Please use this identifier to cite or link to this item:
https://hdl.handle.net/10321/3966
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Akinyemi, Ayodeji Stephen | en_US |
dc.contributor.author | Musasa, Kabeya | en_US |
dc.contributor.author | Davidson, Innocent E. | en_US |
dc.date.accessioned | 2022-05-16T13:26:28Z | - |
dc.date.available | 2022-05-16T13:26:28Z | - |
dc.date.issued | 2022-12 | - |
dc.identifier.citation | Akinyemi, A.S., Musasa, K. and Davidson, I.E. 2022. Analysis of voltage rise phenomena in electrical power network with high concentration of renewable distributed generations. Scientific Reports. 12(1). doi:10.1038/s41598-022-11765-w | en_US |
dc.identifier.issn | 2045-2322 (Online) | - |
dc.identifier.uri | https://hdl.handle.net/10321/3966 | - |
dc.description.abstract | The increasing penetration levels of renewable distributed generation (RDG) into a power system have proven to bring both positive and negative impacts. The occurrence of under voltage at the far end of a conventional electrical distribution network (DN) may not raise concern anymore with RDGs integration into a power system. However, a penetration of RDGs into power system may cause problems such as voltage rise or over-voltage and reverse power flows at the Point of Common Coupling (PCC) between RDG and DN. This research paper presents the impact of voltage rise effect and reverse power flow constraint in power system with high concentration of RDG. The analysis is conducted on a sample DN, i.e., IEEE 13-bus test system, with RDG penetration by considering the most critical scenario such as low power demand in DN and a peak power injection by RDG. For studying the impact of voltage rise and reverse power flow, a mathematical model of a DN integrating RDG is developed. Furthermore, a controller incorporating an advance control-algorithm is proposed to be installed at PCC between DN and RDG to regulate the voltage rise effects and to mitigate the reverse power flow when operating at a worst critical scenario of minimum load and maximum generation from RDG. The proposed control strategy also mitigates the voltageācurrent harmonic distortions, improves the power factor, and maintain the voltage stability at PCC. The simulations are carried out using MATLAB/Simulink software. Finally, recommendations are provided for the power producers to counteract the effects of voltage rise at PCC. The study has demonstrated that, voltage at PCC can be sustained with a high concentration of RDG during a worst-case scenario without a reverse power flow and voltage rise beyond grid code limits.</jats:p> | en_US |
dc.format.extent | 22 p. | en_US |
dc.language.iso | en | en_US |
dc.publisher | Springer Science and Business Media LLC | en_US |
dc.relation.ispartof | Scientific Reports; Vol. 12, Issue 1 | en_US |
dc.subject | Voltage | en_US |
dc.subject | Electrical power network | en_US |
dc.subject | Renewable distributed generations | en_US |
dc.title | Analysis of voltage rise phenomena in electrical power network with high concentration of renewable distributed generations | en_US |
dc.type | Article | en_US |
dc.date.updated | 2022-05-12T11:56:45Z | - |
dc.identifier.doi | 10.1038/s41598-022-11765-w | - |
item.grantfulltext | open | - |
item.cerifentitytype | Publications | - |
item.fulltext | With Fulltext | - |
item.openairecristype | http://purl.org/coar/resource_type/c_18cf | - |
item.openairetype | Article | - |
item.languageiso639-1 | en | - |
Appears in Collections: | Research Publications (Engineering and Built Environment) |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Akinyemi_Musasa_Davidson_2022.pdf | Article | 3.24 MB | Adobe PDF | View/Open |
Page view(s)
286
checked on Dec 22, 2024
Download(s)
53
checked on Dec 22, 2024
Google ScholarTM
Check
Altmetric
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.